Introduction:
This manual covers the assembly, installation, start
up, operation and maintenance of the 600, 800 and
1000 remote low side cuber systems.
Eclipseä 600, 800, 1000
April 2002
Page 1
Table of Contents
Configuration: ················· Page 2
Technical Specifications ············ Page 3
Model Number Locations ··········· Page 4
Cabinet Drawings, Ice Making System ···· Page 5
Cabinet Drawings, Compressor Package and
Condensers ·················· Page 6
Proper Combinations: ············· Page 7
Create the System··············· Page 8
System Examples ··············· Page 9
System Examples ··············· Page 10
Place Remote System ············· Page 11
System Location ················ Page 12
Route Tubing ················· Page 13
Ice Making Section ·············· Page 14
Compressor Package ············· Page 15
Condensing Section Assembly ········ Page 16
Condensing Section Assembly: ER2C6810 · Page 17
Condensing Section Assembly ········ Page 18
Ice making section: ·············· Page 19
Water and Drain ················ Page 20
Water and Drain ················ Page 21
Water and Drain ················ Page 22
Ice Making Section Set Up ·········· Page 23
Coupling Connections: ············ Page 24
Condensing Unit Connections ········· Page 25
Final Placement ················ Page 26
Controller Operation ·············· Page 27
Initial Start Up ················· Page 28
Purge Adjustment ··············· Page 29
System Operation:··············· Page 30
Refrigeration Details: ············· Page 31
Technicians Only: Freeze Cycle Sequence of Operation
························· Page 32
Technicians Only: Harvest Cycle Sequence of Operation
························· Page 33
Power and Water Interruptions ········ Page 34
Sanitation and Cleaning ············ Page 35
Other Maintenance ·············· Page 36
Tight Installation Access ············ Page 37
Water Distributors ··············· Page 38
Ice Sensors ·················· Page 39
Water Level Sensor Maintenance ······· Page 40
Service Diagnosis ··············· Page 41
Service Diagnosis ··············· Page 42
Service Diagnosis ··············· Page 43
Controller Features & Last Error Recall ···· Page 44
Operational Characteristics 600 lb system · · Page 45
Operational Characteristics 800 lb system · · Page 46
Operational Characteristics 1000 lb system · · Page 47
Refrigeration System Service ········· Page 48
Przeglądanie stron 0
1 2 3 4 5 6 ... 49 50

Podsumowanie treści

Strona 1 - Eclipseä 600, 800, 1000

Introduction:This manual covers the assembly, installation, startup, operation and maintenance of the 600, 800 and1000 remote low side cuber systems.E

Strona 2

System ExamplesSingle circuit systems use a single circuitcondenser and one CP unit. Two circuit systemsuse a condenser with two circuits with a CP un

Strona 3

Place Remote SystemRoof preparationMost installations of this system will place thecompressor package and condenser on the roof ofa building. The roof

Strona 4

System LocationLimitations:Distance: Limited to the maximum length of asingle pre-charged tubing kit, 75 feet.Condensing Unit Elevation over Ice Makin

Strona 5

Route TubingScotsman’s pre-charged tubing kits are pre-bent tofit the connection path at the ice making section.·If the tubing is to be routed out the

Strona 6

Ice Making SectionThe CME686 and CME810 are similar in layout.They differ in controller, float stem and vapor inletvalve. Both have three plates and t

Strona 7

Compressor PackageBoth compressor packages are similar in layout,they only differ in compressor and charge.Major Components:CPR Valve - limits refrige

Strona 8

Condensing Section Assembly(CP680 to ERC680 or CP1086 to ERC1086):1. Remove cartons from compressor package andcondenser.2. Remove top from both units

Strona 9

Condensing Section Assembly: ER2C6810(CP680 or CP1086 to ER2C6810):1. Remove cartons from compressor package andtwo-circuit condenser.2. Remove top fr

Strona 10

Condensing Section AssemblyAlternate Assembly:The CP unit may be connected to an approvedcondenser coil in a central condenser rack. Inthose cases, th

Strona 11

Ice making section:Remove from carton.Remove all panels.Utility Connection Route:Routing the refrigerant lines, power cord, watersupply and interconne

Strona 12

Configuration:A remote low side cuber system includes severalsub systems: an ice making section, a remotecompressor package, and a remote air cooledco

Strona 13

Water and DrainThe ice making section requires an adequatepotable water supply and a gravity drain.Determine how the water supply and drain will becon

Strona 14

Water and DrainLeft Draining:1. Connect ¾” PVC to the female PVC fitting. Ifcopper is required by code, remove the PVCconnector and install a ¾” FPT f

Strona 15

Water and DrainRight Draining: Remove vinyl hose from barbedfitting at drain fitting. Locate alternate vinyl hose.Attach to barbed fitting and insert

Strona 16

Ice Making Section Set UpRotate the ice making section as needed to accessthe right side, where the refrigeration connectionswill be made. Connect the

Strona 17

Coupling Connections:The couplings on the ends of the pre-charged linesets are self-sealing when installed properly.Follow these instructions carefull

Strona 18

Condensing Unit ConnectionsConnect the suction line, the vapor line and theliquid line to the matching fittings on the CP unit.See Coupling Connection

Strona 19

Final PlacementAfter the utilities and refrigeration connectionshave been made, secure the unit to the dispenseror bin top.Secure ice making section t

Strona 20

Controller OperationThe controller has seven indicator lights and fourpush buttons.Indicator LightsBin Full: On when the bin is full, blinks on and of

Strona 21

Initial Start UpPre StartA soak-out period of four hours is optional for thissystem. If desired, powering the compressor unitfor four hours prior to s

Strona 22

Purge AdjustmentNote: While the amount of water purge isadjustable, only those installations with a watersupply known to be excellent (very low TDS)sh

Strona 23

Technical SpecificationsIce Making Section (IMS)Compressor PackageCondenser* * ERC condenser fan motor is powered from CPunit and the ERC’s ampacity i

Strona 24

System Operation:This section is intended for the technician.Understanding it is not necessary for the normaloperation and maintenance of this ice mak

Strona 25

Refrigeration Details:The compressor provides the force that circulatesrefrigerant in the refrigeration system. Duringfreeze, when the vapor inlet and

Strona 26

Technicians Only: Freeze Cycle Sequence of OperationThis sequence begins with a restart after the unithas shut off with the bin full. Ice has beencons

Strona 27

Technicians Only: Harvest Cycle Sequence of OperationAt the beginning of harvest, the controller:·Shuts off the Freeze light·Turns on the Harvest ligh

Strona 28

Power and Water InterruptionsShort (less than one second) power interruptionscause no change in operation.Longer interruptions initiate a restart proc

Strona 29

Sanitation and CleaningIt is the User’s responsibility to keep the ice machine and ice storage bin in a sanitary condition.Without human intervention,

Strona 30

Other MaintenanceThe remote condenser coil must be cleanedoccasionally to keep the system operating at highefficiency.·Remove any large debris from th

Strona 31

Tight Installation AccessSome installations will have very small access tothe sides and top of the ice making section. Inthose cases, alternative meth

Strona 32

Water DistributorsIt may become necessary to remove the waterdistributors from the top of the evaporator andclean (de-mineralize) them outside of the

Strona 33

Ice SensorsThe ice sensors, located in holders in the base ofthe ice making section, must be clean and free ofmineral scale to provide the controller

Strona 34

Model Number LocationsIce Making SectionThe dataplate on the back of the ice machinecontains the model number, serial number andelectrical data.A seco

Strona 35

Water Level Sensor MaintenanceIn most cases the water level sensor will notrequire maintenance. However, if the area wherethe ice making section is lo

Strona 36

Service DiagnosisEclipseä 600, 800, 1000April 2002Page 41Problem or Symptom Possible Cause Probable CorrectionNo ice No power to ice making section Re

Strona 37

Service DiagnosisEclipseä 600, 800, 1000April 2002Page 42Problem or Symptom Possible Cause Probable CorrectionNo ice No refrigeration, unit shut down

Strona 38

Service DiagnosisEclipseä 600, 800, 1000April 2002Page 43Problem or Symptom Possible Cause Probable CorrectionLow capacity Dirty condenser Clean conde

Strona 39

Controller Features & Last Error RecallLast Error/Diagnostic Light RecallTo recall the last error on the blue housing CM3controller:1. Switch the

Strona 40

Operational Characteristics 600 lb systemCycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees FSystem Pressures @ Condenser Temp/Cabinet Te

Strona 41

Operational Characteristics 800 lb systemCycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.System Pressures @ Condenser Temp/Cabinet T

Strona 42

Operational Characteristics 1000 lb systemCycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees FSystem Pressures @ Condenser Temp/Cabinet T

Strona 43

Refrigeration System ServiceRecoveryRecovery must be done from the condensing unit,but requires the ice machine to be shut down.1. At the ice making s

Strona 44

CME810 Symptom: Ice jams upLikely Cause: End Defl ector Out of PositionThe End Defl ector must be in place as shown here. The End Defl ector routes the i

Strona 45

Cabinet Drawings, Ice Making SystemEclipseä 600, 800, 1000April 2002Page 522.0028.006.583.463.001.7516.75OPTIONAL REAR ACCESSLINE SET, WATER INLET, 12

Strona 46

Subject: CME810 Float Stem Color ChangeThe color of part number 02-3777-04 has been changed from light blue to black.The infrared light of the water l

Strona 47

Cabinet Drawings, Compressor Package and CondensersEclipseä 600, 800, 1000April 2002Page 6BACK VIEWFRONT VIEWRIGHT SIDE VIEW1/2" COOL VAPOR LINE0

Strona 48

Proper Combinations:The three sub systems are designed to beconnected together in certain combinations to meetthe user’s needs:Eclipse 600 System: CME

Strona 49

Create the SystemPlan the installation. The system consists of fourparts: the ice making section, the compressorpackage, the interconnecting tubing an

Strona 50 - SERVICE BULLETIN

System ExamplesThe Eclipse system can be installed on a bin ordispenser. The CP unit can be installed on either asingle circuit condenser, a two circu