Problem Likely Cause Probable Solution
Shut down on
maximum freeze time
Pump hose disconnected Check hose
Compressor not operating
Check compressor contactor,
check controller using test
mode
Check compressor start
components, check PTCR
resistance and temperature
Check compressor voltage
Check compressor windings
Low refrigerant charge
Add some refrigerant and
restart unit. If cycle time
improves, look for leak.
Hot gas valve leaks through
during freeze
Check hot gas valve for hot
outlet during freeze
Thermostatic expansion valve
bulb loose
Check bulb
Thermostatic expansion valve
producing very low or very high
superheat
Check evaporator superheat,
change TXV if incorrect
Compressor inefficient
Check compressor amp draw,
if low and all else is correct,
change compressor
September 2006 Page 43
Diagnostics – Air Cooled